SHORT CIRCUIT FAULT ANALYSIS IN THE ELECTRIC POWER DISTRIBUTION SYSTEM AT PT PLN (Persero) UP3 SOUTH MAKASSAR ULP KALEBAJENG USING ETAP

Authors

  • Nur Annisa Dewi Nayla Universitas Negeri Makassar
  • Riana T Mangesa Universitas Negeri Makassar
  • Andi Imran un
  • Firdaus Universitas Negeri Makassar
  • Zulhajji Universitas Negeri Makassar

DOI:

https://doi.org/10.59562/jeeni.v1i1.420

Keywords:

Power System Analysis, Short Circuit, Single Phase to Ground, ETAP

Abstract

Short circuit fault analysis is needed to determine the amount of short circuit current flowing in a system. This study discusses the single-phase short-circuit current to the ground at the point where the disturbance occurs from the base of the network to the end of the Malewang feeder network. The purpose of this study was to determine the amount of short circuit fault current in the Electric Power Distribution System at PT PLN (Persero) UP3 South Makassar ULP Kalebajeng. This study used the ETAP program and manual calculations. The results of the study found that the contribution of the largest single-phase short-circuit fault current to the ground in the Malewang feeder occurred on Buses located at the base of the network close to the Substation, namely Bus 1 (Exim-Rec Kalaserena) of 0.311 kA, while thesmallest Buscontribution occurred on Buses located at the end of the network far from the Substation, namely Buses 14 (Bilonga) of 0.292 kA. From the results of the study, it can be concluded that the farther the interference bus is from the Substation, the greater the channel impedance. The greater the impedance, the smaller the short-circuit current.

Downloads

Download data is not yet available.

References

J. J. Grainger and Wu. D. Stevenson Jr, Power system analysis. McGraw-Hill series in electrical and computer engineering, 1994.

O. Penangsang and N. K. Aryani, “Penentuan Lokasi Gangguan Hubung Singkat pada Jaringan Distribusi 20 kV Penyulang Tegalsari Surabaya dengan Metode Impedansi Berbasis GIS (Geographic Information System),” Jurnal Teknik ITS, vol. 6, no. 1, pp. B66–B71, 2017.

A. D. Ernia and S. T. Agus Supardi, “Analisa Gangguan Hubung Singkat Pada Sistem Tenaga Listrik Di Pertamina Ep-Central Processing Plant Area Gundih Menggunakan Software Etap 12.6,” Universitas Muhammadiyah Surakarta, 2017.

A. Effendi, “Studi Analisa Gangguan Hubung Singkat 1 Fasa Ke Tanah Pada SUTT 150 KV Untuk Setting Relay OCR (Aplikasi GI PIP–PAUH LIMO),” Jurnal Teknik Elektro, vol. 3, no. 2, pp. 95–104, 2014.

C. Calnela and I. A. Raharjo, “ANALISIS HUBUNG SINGKAT PADA GARDU INDUK 150/20 KV (STUDI KASUS DI GARDU INDUK GANDUL, CINERE),” Journal of Electrical Vocational Education and Technology, vol. 4, no. 2, pp. 53–59, 2019.

F. Firdaus, A. Imran, R. T. Mangesa, and F. S. Waruru, “Protection System Coordination On 20 kV Distribution Network in Makassar City,” PROtek: Jurnal Ilmiah Teknik Elektro, vol. 10, no. 2, p. 65, 2023, doi: 10.33387/protk. v10i2.4204.

H. Saadat, Power System Analysis. 1999. doi: 10.1049/pbpo076e_ch5.

A. S. Purnomo and A. Budiman, “Studi Kapasitas Hubung Singkat Satu Fasa Ke Tanah Pada Penyulang 5 Pt Pln (Persero) Up3 Tarakan,” Jurnal: Elektrika Borneo (JEB), vol. 7, no. 1, pp. 23–27, 2021.

M. D. Kuncahyo, “Analisis Setting Ground Fault Relay (GFR) Terhadap Sistem Pentanahan Netral Transformator Menggunakan Metode Neutral Grounding Resistor (NGR) pada Penyulang PLN Rayon Kuala Pembuang Kalimantan Tengah,” vol. 01, no. September, pp. 15–22, 2017.

R. S. Lau, “Implementasi Sistem Grounding Ngr Pada Generator Untuk,” pp. 1–11, 2019.

SPLN, “SPLN 2: 1978 Pentanahan Netral Sistem Transmisi, Sub-Transmisi dan Distribusi Besarta Pengamanannya,” in Departemen Pertambangan dan Energi Perusahaan Umum Listrik Negara, Jakarta, 1978, pp. 1–12.

L. Ali, Aksan, and A. R. Sultan, “Analisis Gangguan Hubung Singkat Pada Jaringan Distribusi 20 Kv Di Gardu Induk Daya,” Jurnal Ilmiah Flash, vol. 5, no. 1, pp. 16–22, 2019.

J. Lewis Blackburn and T. Domin, Proctetive Relaying: Principles and Applications, vol. 23, no. 4. 2006.

A. F. Setiawan, “Analisis Arus Gangguan Hubung Singkat Untuk Memprediksi Lokasi Gangguan Pada Saluran Distribusi PT PLN (Persero) Unit Layanan Pelanggan Bandarjaya,” Universitas Lampung, 2021.

Downloads

Published

2023-08-21